Product Code: CA736
Available In 3-7 Days
C-Tec CA736 EACIE 1 Way Flat Interface - Double Gang
A loop-powered single way flat interface for use on a C-TEC EVAC-ALERT system which can control one or more evacuation alert devices located inside a flat.
Key Features
Reliable hard-wired technology
Compatible with the self-test facility on C-TEC’s BF430/EA and BF433C/EA range of self-testing evacuation alert devices
Provides one open & short circuit fault monitored conventional sounder circuit (faults are indicated on the CA736 and reported back to the host EVAC-ALERT panel)
Mounts on a standard UK 35mm double gang back box outside the flat for BS 8629 Clause 8 compliance
50mA alarm current – can power up to 8 evacuation alert sounders (most sites require only one alert sounder so this allows additional alert devices to be connected, e.g. for the hard of hearing)
Polling, Sounder Circuit Active and Input Fault indicators
On-board short circuit loop isolator
| UK Mainland | Order by 2pm for Next Day Delivery* |
|---|---|
| Under £25.00 | £4.50 |
| Over £25.00 | FREE |
| UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
|---|---|
| Under £80.00 | £15.00 |
| Over £80.00 | FREE |